Weight transmitter PR5215
Housing Plug-in COMBICOM screw terminals for max. 2.5 mm² IP20
Installation on 35-mm top hat rail in accordance with DIN 46277
Dimensions 117 × 50 x 117 mm
Power supply 24 VDC +10/-15%
Power consumption Max. 9 W
Display 1.77” TFT LCD, 30 x 37 mm
Control outputs Quantity: 3, optocoupler isolated, passive, max. 30 VDC, max. 30 mA
Function: limits, status, weight, etc.
Control inputs Quantity: 3, optocoupler isolated, max. 30 VDC, max. 10 mA
Function: zero, tare, etc.
Load cell connection All strain gauge load cells; 6 or 4-wire connection is possible
Load cell supply 5 VDC (±2,5 VDC), short-circuit-proof
Load impedance Min. 75 Ω, e.g. 4 load cells each with 350 Ω
Measuring principle Measuring amplifier: Delta-Sigma converter
Measurement time: min. 10 ms - max.640 ms
Sensitivity Smallest usable measurement signal 0.5 μV/d
Input signal 0 to 20 mV (for 100% maximum capacity)
Linearity < 0.01%
Temperature effect Zero point Tk0m <0.01% /10K @ 1mV/V
Measuring range TKspan <±4 ppm/K
Digital filter for load cell connection 4th order (low pass), Bessel, aperiodic or Butterworth
Ethernet interface TCP/IP web service for configuration
ModBus TCP IP address via DHCP or fixed input
Field bus /01 and /11: Profibus-DP-V0, 9-pin D-Sub female
/04: DeviceNet, 5-pin terminal
/05: CC Link, 5-pin terminal
/06: ProfiNet, RJ45
/07: Ethernet IP, RJ45
/08: EtherCAT, RJ45
Analogue output 0/4 … 20 mA
Resolution of 20,000 divisions at 20 mA
Load impedance 500 Ω max.
Function freely configurable
Serial interface RS 485
Protocol:
Remote displays f