Contact for quote
DOWNLOAD DOCUMENT

Weight transmitter PR 5211
Technical specifications
Parameter Description
Housing – Plug-in COMBICOM screw terminals, IP20
– Installation on 35 mm top hat rails in accordance with DIN 46277
– ROHS compliant
Dimensions 99×116×45 mm
Power supply 24 VDC, +10/-15%
Power consumption Max. 8.2 W
Status display Status LEDs for operational readiness, communication activity, etc.
Control outputs Quantity: 3, optocoupler isolated, passive, max. 30 VDC, max. 30 mA
Function: limits, weight status, etc.
Control inputs Quantity: 3, optocoupler isolated, max. 30 VDC, max. 10 mA
Function: zero, tare, etc.
Load cell connection All strain gauge load cells; 6 or 4-wire connection is possible
Load cell supply 12 VDC (±6 VDC), short-circuit-proof, external load cell supply possible
Load impedance – min. 75 Ω
– e.g. six load cells with 600 Ω each or four load cells with 350 Ω each
Measuring principle Measuring amplifier: Delta-Sigma converter
Measurement time: min. 10 ms–max. 1920 ms
Sensitivity Internal: 7.5 nV (~ 4.8 million parts)
Usable resolution: 0.2 μV/d
Input signal 0 to 36 mV (for 100% maximum capacity)
Linearity < 0.002%
Temperature effect Zero point TK0m: <0.02 μV/K RTI
Measuring range TKspan: <±2 ppm/K
Digital filter for load cell connection 4th order (low pass), Bessel, aperiodic or Butterworth
USB interface Implementation: USB 1.1, type B
Function: configuration on the PC via ConfigureIT!
Analogue output (PR 5211/00, ../10) – 0/4…20 mA,
– Internal resolution 16 bit
– Usable step width 0.5 μA
– Load impedance 500 Ω max.
– Function freely configurable
Serial Interface RS485 Implementation: screw terminals for up to 2.5 mm2
, plug-in, Phoenix/COMBICON system
Protocol: remote display, SMA
ProfiBus DP interface (PR 5211/00, ../11) 12 Mbit, DP-V0
IEC 61158 Type 3 and IEC 61784
Ambient temperature range Operation: -10…+55°C
Storage: -40…+70°C
Packaging dimensions 210×140×65 mm
Weight Net: 0.29 kg